45
Input Type Selection
12
12.2 INPUT TYPE: ( RTD )
ENTER INPUT TYPE MENU:
Press ‘MENU 1) Display shows "INPUt" Input Menu.
Press ‘RESET/ENTER 2)
Display flashes "VOLt" (default) or previous stored input type.
Press ‘/MAX 3) Scroll through the available following input type selection list. Display
flashes:
"VOLt" (DC Voltage)
"CURRNt" (DC Current)
"bRIdGE" (Bridge)
"POt" (Potentiometer)
"tC" (Thermocouple)
"Rtd" (RTD)
If the displayed input type is "Rtd", press ‘RESET/ENTER to skip to Step 6
("Rtd" stops flashing).
Rtd "Rtd" RTD SUBMENU:
Press ‘/MAX 4) Scroll through the available selection to "Rtd" (flashing).
Press ‘RESET/ENTER 5) Display shows "StOREd" stored message momentarily and then "Rtd"
(not flashing).
Press ‘RESET/ENTER 6) Display flashes previous RTD type selection. ie. "2Pt 392" default
(see Table below for types). If the display matches your choice of RTD
type. Go to Step 8
Press ‘/MAX 7) Scroll through the available RTD types to the selection of our choice.
Press ‘RESET/ENTER 8) Display shows "StOREd" stored message momentarily and then
advances to the "RdG.CNF" Reading Configuration Menu.
Display RTD types
2Pt 392
2 wire, 100 Ohms, NIST RTD, alpha=0.00392
3Pt 392 3 wire, 100 Ohms, NIST RTD, alpha=0.00392
4Pt 392 4 wire, 100 Ohms, NIST RTD, alpha=0.00392
2Pt 385 2 wire, 100 Ohms, NIST RTD, alpha=0.00385
3Pt 385 3 wire, 100 Ohms, NIST RTD, alpha=0.00385
4Pt 385 4 wire, 100 Ohms, NIST RTD, alpha=0.00385
3.L INR 3 wire, linear RTD
4.L INR 4 wire, linear RTD